ADV/MATE/AGS/LS-----------------
load stop 0 kw
DOWN UP INC DEC
ADV/MATE/AGS/LS----------------
load stop 1 min
delay
DOWN UP INC DEC
ADV/MATE/AGS/LS---------------
end of the LOAD
START menu
UP TOP AGS
Load Stop Delay
Load Stop KW
AnAGSstopcommandwillbeissuedwhenthe
totalACloadofalltheFXsconnectedtothe
MATE falls below this setting for the amount of
time set with load stop delay (nextscreen)aslong
asthegeneratorwasstartedduetoLoadStart.
issettingexcludesanyFXchargercurrent
for its AC load calculation. e setting can be
changed using the <INC> and <DEC> so keys.
Pressing the <DOWN> so key leads to the load
stop delay screen.
is setting is the delay time the total system AC
loadmustremainbelowtheLoadStopkwbefore
thegeneratorisstopped.Itisadjustablefrom1to
240minutesusingthe<INC> and <DEC> keys.
Pressing the <DOWN> so key leads to the end of
the VOLTAGE START menu screen.
Pressing the <AGS>sokeyreturnstheADV/
MATE/AGS/PG2screen
Zobrazit stránku 87