66 900-0161-01-00 Rev A
Table 16 Radian Inverter Settings
Field Item Default Minimum Maximum
Gen AC Input
Mode and Limits
Input Mode Generator
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit Lower
108 Vac 85 Vac 110 Vac
(Voltage Limit) Upper
140Vac 125 Vac 140 Vac
Transfer Delay
1.0 second 0.12 seconds 4.0 seconds
Connect Delay
0.5 minutes 0.2 minutes 25.0 minutes
If Mini Grid mode
is selected:
Connect to Grid
48.0 Vdc 44.0 Vdc 64.0 Vdc
(Connect) Delay
10 minutes 2 minutes 200 minutes
If Grid Zero mode
is selected:
DoD Volts
48.0 Vdc 44.0 Vdc 64.0 Vdc
DoD
Amps
GS8048A
5 Aac 1 Aac 30 Aac
GS4048A
5 Aac 1 Aac 15 Aac
AC Output
Output Voltage X
120 Vac 100 Vac 130 Vac
AC Coupled Mode
This selection is inoperative
Low Battery
Battery Charger
57.6 Vdc 44.0 Vdc 64.0 Vdc
(Float)
1.0 hours 0.0 hours 24/7
49.6 Vdc 44.0 Vdc 64.0 Vdc
Battery Equalize
Auxiliary Output
or
Aux Mode Vent Fan
Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,
DC Divert, GT Limits, Source Status, AC Divert
(Load Shed)
(Load Shed ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Load Shed)
44.0 Vdc 40.0 Vdc 56.0 Vdc
44.0 Vdc 40.0 Vdc 56.0 Vdc
(Gen Alert ON)
(Gen Alert OFF)
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert)
(DC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(AC Divert ON)
(AC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(AC Divert OFF)
0.5 minutes 0.1 minutes 25.0 minutes
Auxiliary
Relay
Aux Mode
Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,
DC Divert, GT Limits, Source Status, AC Divert
(Load Shed ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert)