Specifications
68 900-0145-01-01 Rev A
Table 16 Radian Inverter Settings
Field Item Default Minimum Maximum
AC Output
Output Voltage
X
230 Vac
200 Vac
260 Vac
AC Coupled Mode
This selection is inoperative
Low Battery
Cut-Out Voltage
42.0 Vdc 36.0 Vdc 48.0 Vdc
Cut-In Voltage
50.0 Vdc 40.0 Vdc 56.0 Vdc
Battery Charger
Absorb Voltage
57.6 Vdc
44.0 Vdc
64.0 Vdc
(Absorb) Time
1.0 hours
0.0 hours
24.0 hours
Float Voltage
54.4 Vdc 44.0 Vdc 64.0 Vdc
(Float) Time
1.0 hours
0.0 hours
24/7
Re-Float Voltage 54.4 Vdc 44.0 Vdc 64.0 Vdc
Re-Bulk Voltage
49.6 Vdc
44.0 Vdc
64.0 Vdc
Battery Equalize
Equalize Voltage
58.4 Vdc
44.0 Vdc
68.0 Vdc
(Equalize) Time
1.0 hours
0.0 hours
24.0 hours
Auxiliary Output
Aux Control
Auto
Off, Auto or On
Aux Mode Vent Fan
Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,
DC Divert, GT Limits, Source Status, AC Divert
(Load Shed) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Load Shed ON) Delay
0.5 minutes
0.1 minutes
25 minutes
(Load Shed) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(Load Shed OFF)
Delay
0.5 minutes 0.1 minutes 25 minutes
(Gen Alert) ON: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(Gen Alert ON) Delay
0.5 minutes 0.1 minutes 25 minutes
(Gen Alert)
OFF: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Gen Alert OFF) Delay 0.5 minutes 0.1 minutes 25 minutes
(Vent Fan)
ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(Vent Fan) Off Delay
0.5 minutes
0.1 minutes
25 minutes
(DC Divert) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(DC Divert ON)
Delay
0.5 minutes
0.1 minutes
25 minutes
(DC Divert) OFF: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(DC Divert OFF)
Delay
0.5 minutes 0.1 minutes 25 minutes
(AC Divert) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(AC Divert ON) Delay
0.5 minutes
0.1 minutes
25 minutes
(AC Divert) OFF: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(AC Divert OFF) Delay
0.5 minutes 0.1 minutes 25 minutes
Auxiliary
Relay
Aux Control
Auto
Off, Auto
or
On
Aux Mode Gen Alert
Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,
DC Divert, GT Limits, Source Status, AC Divert
(Load Shed)
ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(Load Shed ON) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(Load Shed) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(Load Shed OFF) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(Gen Alert) ON: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(Gen Alert ON)
Delay
0.5 minutes
0.1 minutes
25.0 minutes
(Gen Alert) OFF: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Gen Alert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Vent Fan) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Vent Fan) Off Delay
0.5 minutes
0.1 minutes
25.0 minutes
(DC Divert)
ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(DC Divert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(DC Divert OFF) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(AC Divert) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(AC Divert ON)
Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) OFF: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(AC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes